2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 80070101-030302ff : Sensor CPU 3 Overtemp transitioned from normal to non-critical state.
The temperature of microprocessor 3 has exceeded its specified threshold.
May also be shown as 80070101030302ff or 0x80070101030302ff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix: PLAT ID: 0520
User Response
Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 80070101-0303ffff : Sensor CPU 3 Overtemp transitioned from normal to non-critical state.
The temperature of microprocessor 3 has exceeded its specified threshold.
May also be shown as 800701010303ffff or 0x800701010303ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix: PLAT ID: 0520
User Response
Complete the following steps until the problem is solved:
Lenovo Flex System x440 Compute NodeInstallation and Service Guide
296