Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Voltage
SNMP Trap ID
1
CIM Information
Prefix: PLAT ID: 0480
User Response
Replace the CMOS battery.
• 80010701-3701ffff : Numeric sensor [NumericSensorElementName] going high (upper non-critical)
has asserted.
The inlet 1 temperature has exceeded its specified threshold.
May also be shown as 800107013701ffff or 0x800107013701ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix: PLAT ID: 0490
User Response
Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 80010701-3702ffff : Numeric sensor [NumericSensorElementName] going high (upper non-critical)
has asserted.
The inlet 2 temperature has exceeded its specified threshold.
May also be shown as 800107013702ffff or 0x800107013702ffff
Severity
Lenovo Flex System x440 Compute NodeInstallation and Service Guide
286