Lenovo Flex System x440 Compute Node Installation And Service Manual page 329

Table of Contents

Advertisement

CIM Information
Prefix: PLAT ID: 0524
User Response
Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. If there are no other thermal issues, replace the I/O expansion adapter.
• 80070301-2d01ffff : Sensor PCH Overtemp has transitioned to non-recoverable from a less severe
state.
A temperature has exceeded its specified threshold. The compute node will attempt a soft shutdown.
May also be shown as 800703012d01ffff or 0x800703012d01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 8007030d-0b01ffff : Sensor [SensorElementName] has transitioned to non-recoverable from a less
severe state.
There is(are) failed drive(s) causing RAID offline and data lost.
May also be shown as 8007030d0b01ffff or 0x8007030d0b01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
.
Chapter 6
Troubleshooting
319