Number of devices to be installed on the line
The maximum number of devices that can be connected on the detection line is
the following:
99 detectors
99 input/output modules
Features of the output relays
FUNCTION
Siren
General alarm
General trouble
CN0 terminal board
Description
21
RL NA-NC Alarm
RL
Common
20
19
RS232 GND
18
RS232 RI
17
RS232 RX
16
RS232 RTS
15
RS232 RTX
14
GND User
13
+24Vdc User
12
RL Negative Siren
11
RL Positive Siren
10
RL Common trouble
9
RL NA-NC trouble
8
GNDI
7
RS485 LIN-
6
GNDI
5
RS485 LIN+
4
Line 1 B-
3
Line 1 B+
2
Line 1 A-
1
Line 1 A+
AM-1000
AM1000_manu
FEATURES
1 24 Vdc / 1 A supervised contact.
Max 1 A 30Vdc , NA-NC selectable by JALL jumper
Max 1 A 30Vdc , NA-NC selectable by JGST jumper
Features
1A 30Vdc contact
Alarm
Non opto-isolated serial output (if the
connected devices have the negatives
earthing will appear the signal "
Trouble" ).
Protected by 1A Fast fuse
Protected by 0,75A fuse
(polarity inversion output).
1A 30Vdc contact
Opto-isolated serial output
LINE 1
Installation manual
Doc. M-145.1-AM1000-ENG Rev A.2
Notes
NA-NC selectable by
JALL jumper
Earth
Current at disposal of the
user (sum of the two
outputs).
NA-NC to be select
through JGST jumper.
Available function with
the insertion of the
optional AM1SE board.
PAGE - 3