10.5

JOG operation

The frequency and acceleration/deceleration time for JOG operation can be set.
JOG operation can be used for conveyor positioning, test operation, etc.
Pr.
Name
15
Jog frequency
D200
16
Jog acceleration/
F002
deceleration time
These parameters can be selected from among simple mode parameters when the LCD operation panel (FR-LU08) or the
parameter unit (FR-PU07) is connected to the inverter.
*1
60 Hz is initially set in Pr.20 in Group 1, and 50 Hz in Group 2. (Refer to
 JOG operation by inputting signals (JOG signal and JOG2 signal)
• Operation can be started and stopped by the start signals (STF and STR signals) when the Jog operation selection (JOG)
signal or Jog operation selection 2 (JOG2) signal is ON. (For the operation method, refer to
• The JOG signal can be input only via a control circuit terminal. For the JOG signal, set "5" to any parameter from Pr.178
to Pr.184 (Input terminal function selection) to assign the function to a control circuit terminal.
• The JOG2 signal can be input via a control circuit terminal or via communication. For the JOG2 signal, set "30" to any
parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the function to a control circuit terminal.
• Use the JOG acceleration/deceleration time function (Pr.16) to set the acceleration/deceleration time for JOG operation.
Output frequency(Hz)
Pr.20
Pr.15
Forward
rotation
setting range
Pr.16
JOG/JOG2 signal
Forward rotation STF
ON
Reverse rotation STR
 JOG operation using the PU
• When the operation panel or parameter unit is in the JOG operation mode, the motor jogs only while a key for start
command is pressed. (For the operation method, refer to
Initial
Setting range
value
5 Hz
0 to 590 Hz
0.5 s
0 to 3600 s
Time
Reverse
rotation
ON
ON
Description
Set the frequency for JOG operation.
Set the motor acceleration/deceleration time during JOG operation.
The acceleration/deceleration time is a period of time that the
inverter takes to increase/decrease the output frequency to the
frequency set in Pr.20 Acceleration/deceleration reference
*1
frequency
.
The acceleration/deceleration times cannot be set separately.
page
54).
page
49.)
10. (D) Operation Command and Frequency Command
page
48.)
10.5 JOG operation
1
2
3
4
5
6
7
8
9
10
301