Basic Operation
This chapter explains the basic operation of this product.
Always read the instructions before use.
2.1

Operation panel

2.1.1
Components of the operation panel
 Standard model
The operation panel cannot be removed from the inverter.
(i)
(j)
(k)
(n)
No.
Appearance
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
20
2. Basic Operation
2.1 Operation panel
(a)
(b)
(c)
(l)
(m)
Name
Shows a numeric value (readout) of a monitor item such as the frequency or a parameter
Monitor (4-digit
number.
LED)
(The monitor item can be changed according to the settings of Pr.52, Pr.774 to Pr.776.)
Hz: ON when the actual frequency is monitored. (Blinks when the set frequency is monitored.)
Unit indication
A: ON when the current is monitored.
(Both "Hz" and "A" are OFF to indicate a value other than the frequency or the current.)
PU: ON when the inverter is in the PU operation mode.
Inverter operation
EXT: ON when the inverter is in the External operation mode. (ON when the inverter in the initial
mode LED
setting is powered ON.)
indicator
NET: ON when the inverter is in the Network operation mode.
PU and EXT: ON when the inverter is in the External/PU combined operation mode 1 or 2.
Operation panel
MON: ON or blinks only when the first, second, or third monitor is displayed.
mode LED
PRM: ON when the operation panel is in the parameter setting mode. The indicator blinks when
indicator
the inverter is in the easy setting mode.
ON or blinks during inverter running.
ON: During forward rotation operation.
Operating status
Blinks slowly (1.4-second cycle): During reverse rotation operation.
indicator
Blinks quickly (0.2-second cycle): Operation is disabled although the start command is given.
ON when the inverter is set to control the PM motor.
Controlled motor
The indicator blinks during test operation. The indicator is OFF when the inverter controls the
type LED indicator
induction motor.
PLC function LED
ON when the PLC function of the inverter is valid. (The indicator blinks when a fault occurs
indicator
while the PLC function is valid.)
The setting dial of the Mitsubishi Electric inverters. Turn the setting dial to change the setting
of frequency or parameter, etc.
Press the setting dial to perform the following operations:
Setting dial
• To display a set frequency on the LED display in the monitor mode. (The monitor item shown
on the display can be changed by using Pr.992.)
• To display the present setting during calibration.
Switches between the PU operation mode, the PUJOG operation mode, and the External
operation mode.
PU/EXT key
The easy setting of the inverter operation mode is enabled by pressing this key simultaneously
with the MODE key.
Also cancels the PU stop warning.
(d)
(e)
(f)
(g)
(h)
Description
*1