NOTE
• The automatic restart after instantaneous power failure function, orientation control, and emergency drive function do not
operate when brake sequence is selected.
• To use this function, set the acceleration/deceleration time to 1 second or longer.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) or Pr.190 to Pr.197 (Output
terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.
 Setting the brake sequence operation
• Set Pr.292 Automatic acceleration/deceleration = "7 or 8 (braking sequence operation)".
To ensure sequence operation, it is recommended to use with Pr.292 = "7" (with brake opening completion signal input).
• Set "15" in any parameter from Pr.178 to Pr.189 (Input terminal function selection), and assign the Brake opening
completion (BRI) signal to an input terminal.
• Set "20" (positive logic) or "120" (negative logic) in any parameter from Pr.190 to Pr.197 (Output terminal function
selection), and assign the Brake opening request (BOF) to an output terminal.
• Use Pr.639 Brake opening current selection to select whether the output current or the motor torque is used as a
reference for the brake opening operation.
• Under Real sensorless vector control or Vector control, use Pr.640 Brake operation frequency selection to select
whether the frequency command or the actual motor speed (estimated value) is used as a reference for brake closing
operation. If the brake operation timing is different from the motor speed because of the load, set Pr.640 = "1 (brake
operation with the actual motor speed (estimated value))".
• Under Advanced magnetic flux vector control or encoder feedback control, the frequency command is used as a reference
for brake operation regardless of the Pr.640 setting.
NOTE
• Under torque control, the brake sequence function is disabled.
 Operation with brake opening completion signal input (Pr.292 = "7")
• When the start signal is input to the inverter, the inverter starts running, and when the output frequency reaches the
frequency set in Pr.278 Brake opening frequency and the output current or the motor torque is equal to or greater than
the Pr.279 Brake opening current setting, the brake opening request signal (BOF) is output after the time set in Pr.280
Brake opening current detection time. The Brake opening completion (BRI) signal is input, and the output frequency is
increased to the set speed after the set time in Pr.281 Brake operation time at start.
• When the inverter decelerates to the frequency set in Pr.282 Brake operation frequency during deceleration, the inverter
turns OFF the brake opening request signal (BOF) and decelerates further to the frequency set in Pr.278. After
electromagnetic brake operation completes and the inverter recognizes the turn OFF of the BRI signal, the inverter holds
the frequency set in Pr.278 for the time set in Pr.283 Brake operation time at stop. And after the time set in Pr.283
passes, the inverter decelerates again. The inverter outputs is shut off when the frequency reaches Pr.13 Starting
frequency setting or 0.5 Hz, whichever is lower.
Output current or motor torque
458
15. (A) Application Parameters
15.1 Brake sequence function
Output frequency(Hz)
Target frequency
Pr.282
Pr.278
Pr.13
STF
(select by Pr.639)
Brake opening request
(BOF signal)
Brake opening completion
(BRI signal)
Closed
Electromagnetic brake
operation
Pr.280
Pr.281
ON
Pr.279
ON
ON
Opened
Pr.13 setting
or 0.5Hz,
whichever is lower
Time
Pr.283
Closed