Download Print this page

Mitsubishi Electric FR-E800 Instruction Manual page 412

Advertisement

 Input terminal function assignment
• Signals can be input to the inverter by using physical terminals (except for the FR-E800-SCE) or via communication, or
assigned to the extension terminals of the plug-in option (FR-E8AXY). Option input terminals are not available for the IP67
model as plug-in options are not available.
• Use parameters to assign functions to input terminals. Check the terminal available for each parameter.
Terminal
Pr.
name
FR-E800
178
STF/DI0
○ (STF)
179
STR/DI1
○ (STR)
180
RL
181
RM
182
RH
183
MRS
184
RES
185
NET X1
186
NET X2
187
NET X3
188
NET X4
189
NET X5
525
X1
526
X2
527
X3
528
X4
529
X5
530
X6
531
X7
○: Assignment/input available, ─: Assignment/input unavailable (no function)
*1
The communication protocol affects which terminals can be used. For details, refer to the Instruction Manual (Communication) or the Instruction
Manual of each communication option.
*2
Refer to the Instruction Manual of the option for details on the option input terminals.
 Input signal list
• Refer to the following table and set the parameters.
Signal
Setting
name
Pr.59 = "0" (initial value)
0
RL
Pr.59 ≠ "0"
Pr.270 = "1, 11"
Pr.59 = "0" (initial value)
1
RM
Pr.59 ≠ "0"
Pr.59 = "0" (initial value)
2
RH
Pr.59 ≠ "0"
Second function selection
3
RT
Pr.270 = "1, 11"
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
7
OH
External thermal relay input
15-speed selection (Combination with multi-speeds of RL, RM, and
8
REX
RH)
10
X10
Inverter run enable (FR-XC/FR-HC2/FR-CV connection)
12
X12
PU operation external interlock
External input terminal (physical terminal)
FR-E800-E
FR-E800-SCE
○ (DI0)
○ (DI1)
Function
Low-speed operation command
*1
Remote setting (setting clear)
*2
Stop-on-contact selection 0
Middle-speed operation
command
*1
Remote setting (deceleration)
High-speed operation command
*1
Remote setting (acceleration)
*2
Stop-on-contact selection 1
*3
Input via
communication
FR-E806
Forward rotation
○ (DI0)
command only
Reverse rotation
○ (DI1)
command only
Related parameter
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.59
Pr.270, Pr.275, Pr.276
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.59
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.59
Pr.44 to Pr.48, Pr.51, Pr.450
to Pr.463, Pr.569, Pr.832,
Pr.836, etc.
Pr.270, Pr.275, Pr.276
Pr.267
Pr.15, Pr.16
Pr.9
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.17, Pr.30, Pr.70
Pr.79
13. (T) Multi-Function Input Terminal Parameters
13.6 Input terminal function selection
Option input terminal
*2
(physical terminal)
*1
FR-E8AXY
Refer to
page
303
269
461
303
269
303
269
418
461
392
301
306
303
545
280
11
12
13
14
15
16
17
18
19
20
411

Advertisement

loading