Mitsubishi Electric FR-E800 Instruction Manual page 141

Advertisement

Pr.
Name
816
Torque limit level during
H720
acceleration
817
Torque limit level during
H721
deceleration
858
Terminal 4 function
T040
assignment
874
OLT level setting
H730
*1
The initial value changes from 150% to 200% when the control method is changed from V/F control or Advanced magnetic flux vector control to
Real sensorless vector control or Vector control in the FR-E820-0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, FR-E860-0061(3.7K) or
lower, FR-E820S-0110(2.2K) or lower, FR-E810W-0050(0.75K) or lower, and FR-E846-0095(3.7K) or lower.
*2
CC-Link communication is unavailable when the Vector control compatible option is installed or when the IP67 model is used. (For the details of
the CC-Link communication, refer to the FR-A8NC E kit Instruction Manual. For details on communication protocols, refer to the Instruction
Manual (Communication).)
NOTE
• The lower limit for the torque limit level under Real sensorless vector control is set to 30% even if a value lower than 30% is set.
• Under PM sensorless vector control, the torque limit is not activated in a low-speed range with a rated frequency of less than
10%.
• Under PM sensorless vector control, the torque limit level is reduced inversely proportional to the output frequency in the
constant output range of the rated motor frequency or higher.
 Block diagram of torque limit
 Selecting the torque limit input method (Pr.810)
• Use Pr.810 Torque limit input method selection to select the method to limit the output torque for speed control.
The method in the initial setting is use of the parameter settings.
Pr.810 setting
0 (initial value)
1
2
 Internal torque limit 1 (Pr.810 = "0", Pr.812 to Pr.814)
• The torque is limited by parameter setting
• In the initial value, a limit is applied to all quadrants by Pr.22 Stall prevention operation level (Torque limit level).
140
5. Speed Control
5.4 Setting the torque limit level
Initial value
9999
9999
0
150%
<Vector control>
Speed command +
-
Torque limit input
method
Perform the torque limit operation using the parameter (Pr.22, Pr.812 to Pr.814) settings.
Internal torque limit 1
If changing the torque limit parameters via communication is enabled, the torque limit input
can be performed via communication.
External torque limit
Torque limit using analog voltage (current) to terminal 4 is valid.
• The setting value of Pr.805 or Pr.806 is used as the torque limit value.
(Internal torque limit 2)
• The torque limit via communication is enabled.
Setting
range
0% to 400%
Set the torque limit value during acceleration.
9999
The same torque limit as constant speed.
0% to 400%
Set the torque limit value during deceleration.
9999
The same torque limit as constant speed.
The torque limit level can be changed with setting value "4" and the
0, 4, 6, 9999
signal to terminal 4.
The inverter can be set to be shut off at activation of torque limit
0% to 400%
and stalling of the motor. Set the output to be shut off.
Torque limit
Speed control
Description
Iq current control
M
Encoder
Operation