16.8
Regenerative brake selection
• When performing frequent start and stop operation, usage rate of the regenerative brake can be increased by using the
optional high-duty brake resistor (FR-ABR) or the brake unit (FR-BU2, BU, or FR-BU).
• The multifunction regeneration converter (FR-XC in power regeneration mode) or power regeneration common converter
(FR-CV) is used for the continuous operation in the regenerative status. The multifunction regeneration converter (FR-XC
in common bus regeneration mode) and high power factor converter (FR-HC2) can also be used to reduce harmonics,
improve power factor, and operate continuously during regenerative driving. The multifunction regeneration converter (FR-
XC), power regeneration common converter (FR-CV), and high power factor converter (FR-HC2) cannot be used with the
safety communication model and the IP67 model.
• When the FR-E8DS is installed, the reset operation when the power is supplied to the main circuit while 24 V external
power is supplied to the inverter can be selected. (Standard model and Ethernet model)
Pr.
Name
Regenerative
30
function
0
E300
selection
Special
70
regenerative
0%
G107
brake duty
MRS/X10
17
terminal input
0
T720
selection
*1
Available for the standard model and the Ethernet model.
Initial
Setting
value
range
No regenerative function
0
Brake resistor (MRS, MYS type)
Brake unit (FR-BU2)
Multifunction regeneration converter (FR-XC)
Power regeneration common converter (FR-CV)
*1
100
High power factor converter (FR-HC2)
1
Brake resistor (MYS type) used at 100% torque, 6%ED
High-duty brake resistor (FR-ABR)
*1
101
*1
2
When the automatic restart operation after instantaneous
power failure function is enabled while a brake resistor and a
regeneration unit is used
*1
102
0% to 100% Set the %ED of the built-in brake transistor operation.
0
X10: Normally open input
X10: Normally closed input (NC
1
contact input specification)
2
X10: Normally open input
X10: Normally closed input (NC
3
contact input specification)
4
X10: Normally open input
X10: Normally closed input (NC
5
contact input specification)
Description
Reset when power is
supplied to the main
circuit
No reset when
power is supplied to
the main circuit
Reset when power is
supplied to the main
circuit
No reset when
power is supplied to
the main circuit
Reset when power is
supplied to the main
circuit
No reset when
power is supplied to
the main circuit
MRS: Normally open input
MRS: Normally closed input (NC contact
input specification)
External terminal: Normally closed input (NC
contact input specification)
Communication: Normally open input
16. (G) Control Parameters
16.8 Regenerative brake selection
11
12
13
14
15
16
17
18
19
20