Output Frequency Detection - Mitsubishi Electric FR-E800 Instruction Manual

Advertisement

12.7

Output frequency detection

If the inverter output frequency which reaches a specific value is detected, the relative signal is output.
Pr.
Name
41
Up-to-frequency
M441
sensitivity
42
Output frequency
M442
detection
Output frequency
43
detection for reverse
M443
rotation
865
Low speed detection
M446
870
Speed detection
M400
hysteresis
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
 Setting the notification zone of the output frequency reaching the set
point (SU signal, Pr.41)
• The Up to frequency (SU) signal is output when the output frequency reaches the set frequency.
• Set the value in the range of 1% to 100% in Pr.41 to determine tolerance for the set frequency (considered as 100% point).
• It may be useful to use this signal to start operating related equipment after checking that the set frequency has been
reached.
• To use the SU signal, set "1" (positive logic) or "101" (negative logic) in any parameter from Pr.190 to Pr.197 (Output
terminal function selection) to assign the function to an output terminal.
Set frequency
OFF
ON
SU
 Output frequency detection (FU (FB) signal, Pr.42, Pr.43)
• The Output frequency detection (FU) signal and the Speed detection (FB) signal are output when the output frequency
reaches or exceeds the Pr.42 setting.
• The FU signal is useful for applying or releasing electromagnetic brake, etc. Use the Inverter running (RUN) signal when
releasing the brake from the motor with a brake under encoder feedback control. (The brake may not be released when
the FU signal is used.)
• The FU signal is output when the output frequency (frequency command) reaches the set frequency. The FB signal is
output when the detected actual speed (estimated speed under Real sensorless vector control, or feedback value under
Vector control) of the motor reaches the set frequency. The FU signal and the FB signal are output at the same manner
under V/F control or Advanced magnetic flux vector control or during the encoder feedback control operation.
• The frequency detection dedicated to motor rotation in reverse direction is enabled by setting the frequency in Pr.43. This
setting is useful when the timing of the electromagnetic braking during forward rotation operation (for example, during lifting
up in the lifts operation) is different from that during reverse rotation operation (lifting down).
382
12. (M) Item and Output Signal for Monitoring
12.7 Output frequency detection
*1
Initial value
Setting
Gr.1
Gr.2
10%
0% to 100%
6 Hz
0 to 590 Hz
0 to 590 Hz
9999
9999
1.5 Hz
0 to 590 Hz
0 Hz
0 to 15 Hz
Adjustment
range Pr.41
Time
OFF
range
Set the level where the SU signal turns ON.
Set the frequency at which the FU (or FB) signal turns ON.
Set the frequency at which the FU (or FB) signal turns ON only
while the motor rotates in reverse direction.
The frequency same as the Pr.42 setting is set.
Set the frequency at which the LS signal turns ON.
Set the hysteresis width for the detected frequency.
page
54).
Description