2.3

Easy setting of the inverter operation mode

The operation mode suitable for start and speed command combinations can be set easily using Pr.79 Operation mode
selection.
The following shows the procedure to operate with the external start command (STF/STR) and the frequency command by
using the operation panel.
Operating procedure
1.
Press the PU/EXT key and MODE key for 0.5 second at the same time.
Blinking
2.
Turn the setting dial or press the UP/DOWN key until "79-3" (External/PU combined operation mode 1) appears.
(For other settings, refer to the following table.)
Blinking
3.
Press the SET key to confirm the setting. External/PU combined operation mode 1 (Pr.79 = "3") is set.
Operation panel indication
Blinking
Blinking
Blinking
Blinking
NOTE
• When the user group function is used (Pr.160 = "1") or the password function is enabled (with Pr.296 and Pr.297), the easy
setting is disabled (Pr.79 is not displayed).
• "ER2" appears if a setting change is attempted during inverter operation. Turn OFF the start command (the RUN key or STF/
STR signal).
• If the MODE key is pressed before pressing the SET key, the easy setting mode is terminated and the operation panel returns
to the monitor mode. If the easy setting is terminated while Pr.79 = "0 (initial value)", check the inverter operation mode
because the inverter may switch its operation mode between the PU operation mode and the External operation mode.
• Reset by pressing the STOP/RESET key is enabled.
• The following is the frequency commands listed in descending order of priority when "3" is set in Pr.79: Multi-speed setting
function (RL/RM/RH/REX signal) > PID control (X14 signal) > terminal 4 analog input (AU signal) > set frequency (digital input
from the PU).
30
2. Basic Operation
2.3 Easy setting of the inverter operation mode
Operation method
Frequency
Start command
command
Setting dial or UP/
RUN key
DOWN key
External
Analog voltage
(STF/STR signal)
input
External
Setting dial or UP/
(STF/STR signal)
DOWN key
Analog voltage
RUN key
input
Operation mode
PU operation mode
External operation mode
External/PU combined operation mode 1
External/PU combined operation mode 2