The introduced settings for time delay for activation of the panel's outputs must be confirmed with Apply button.
Press Apply button to confirm the set configuration. In the
example: the delay for activation of the sounders will be
turned ON via set time schedule. The delay for activation
of Fire Brigade and Fire Protection outputs is constantly
turned ON.
Use EXIT button to return back to Maintenance Menus.

4.2.4. Review the Log Memory for Events

This menu allows the user to review the system events recorded in the panel's memory log file and to print them if a
printer is available in the panel's configuration. The capacity of the panel's memory log file is 10000 events. In a special
submenu "Clear Log" the user can delete the whole memory log file of the panel.
Enter MAINTENANCE – VIEW LOG menu.
Note: Use Printer button to initiate printing of the log file
from a connected printer. In case no printer is connected
to the panel this button is inoperable.
The user can search for exact events using filters by Date of occurrence and Number.
iRIS8 - Addressable Fire Alarm Panel – User & Maintenance Manual
The time schedule table presents the preprogrammed
hours for turning ON and turning OFF the delay for
activation. At Access Level 2, the user can only review
the set hours for the different days of the week. The time
schedule is set different for every of the outputs.
The events are presented with detailed information about
the type, Zone, Loop and Device number. In case the
panel is connected in a network, the message contains
also information about the panel's number and name in
the system.
The events are displayed from the newest to the oldest
registered in the log file.
The field "Total Alarms Counter" shows the total number
of the registered alarm events in the system.
Use the up and down arrow buttons to scroll the events
one-by-one. In the bottom of the screen are displayed the
number of the event and the date and time of occurrence.
To filter the events by Date of occurrence, press DATE
button and in the new screen enter year/month/day for
search.
Press GO TO button. The View Log screen will return
showing the last registered event for this date.
To filter the events by Number, press NUMBER button
and use the keyboard. Press OK.
The View Log screen will show the contents of the
searched number.