iRIS8 - Addressable Fire Alarm Panel – User & Maintenance Manual
APPENDIX А
Table: Event Messages.
Note: The messages are followed from a Panel, Zone and Loop number, and also Device address, when the event is
received from another panel in the network.
Message
Flash Error
Ram Error
New Periphery Devices Found
Periphery Device Fault
Periphery Device Type Error
AC Loss
Battery Low
Battery Loss
Battery High Resistance
Earth Fault
Charger Fault
Sounder1 Short
Sounder2 Short
Sounder1 Open
Sounder2 Open
Fire Output Short
Fire Output Fault
EXT Output Short
EXT Output Fault
Fault Output Short
Fault Output Fault
Fault Power AUX
Alarm Confirm Input Short
Alarm Confirm Input Open
Alarm Confirm Input On
Protection Alarm Confirm Short
Protection Alarm Confirm Open
Protection Alarm Confirm On
Fault Protection Panel Input Short
Fault Protection Panel Input Open
Fault Protection Panel Input On
Protection Panel Fault
Loop Break
Loop Short
New Loop Devices Found
Loop Zero Address
Double Panel number
Panel Fault
Reset
Silence Alarm
Zone Disabled
Description
FLASH Memory error is detected.
RAM Memory error is detected.
New periphery devices are found in the system configuration.
The device is not responding (the device is lost or failed).
A periphery device with different type is found on the address.
The main power supply is lost.
The accumulator battery is discharged.
The accumulator battery is missing.
High value (Ri>0.3Ω) of the battery internal resistance. Replace the battery
immediately!
Resistive connection between some signals and earth < 10k.
The charging unit is failed.
Short circuit detected at Sounder 1 output.
Short circuit detected at Sounder 2 output.
Circuit broken at Sounder 1 output.
Circuit broken at Sounder 2 output.
Short circuit detected at Fire output.
Circuit broken at Fire output.
Short circuit detected at Extinguishing output.
Circuit broken at Extinguishing output.
Short circuit detected at Fault output.
Circuit broken at Fault output.
Short circuit (the mains power supply is lost).
Short circuit detected at input "Alarm Confirmation".
Circuit broken at input "Alarm Confirmation".
"Alarm Confirmation" input activation.
Short circuit detected at input "Protection Alarm Confirmation".
Circuit broken at input "Protection Alarm Confirmation".
"Protection Alarm Confirmation" input activation.
Short circuit detected at input "Protection Panel Fault".
Circuit broken at input "Protection Panel Fault".
"Protection Panel Fault" input activation.
The extinguishing panel failure.
The loop is broken.
Short circuit detected in the loop.
New loop devices are found in system configuration (Loop 1 or Loop 2).
There is a device without address number (a device with address 0 is applied).
Doubling of the panel number (when two or more panels are connected in a
network).
Fault in the connection with another panel (when two or more panels are
connected
in a network).
Resetting of the panel.
The sounders have been silenced.
The zone is disabled.