4.2.6.4. Sounder Output Test
This is a menu for testing the operability of the monitored sounder outputs on the control panel's PCB.
Note: The Sounder Output Test will be applied to all SND outputs of the used iRIS8 fire alarm panel. The number of the
SND outputs depends on the model and configuration:
- Single panel iRIS8 S (up to 4 loops) – 1 SND output.
- Common configuration of iRIS8 S + iRIS8 Ext (up to 8 loops) – 2 SND outputs. Both panels are mounted
together in a modular structure and connected via interface cable.
- Single panel iRIS8 B (up to 8 loops) – 2 SND outputs.
Enter MAINTENANCE – TEST – SOUNDER OUTPUT TEST.
To start the test, press the ON button.
Use EXIT button to return back to TEST Menus.

4.2.7. Performing Disablements

This is a special maintenance menu for quick access to zones and devices menus and performing disabling/enabling of
the operation. Additional grid view menu for zones and devices makes the reviewing more easer and informative.
The user can also review the addresses of attached devices to zone and loop numbers.
In the last menu, the user can disable/enable the operation of the panel's outputs.
Enter MAINTENANCE- DISABLE menu.
4.2.7.1. Zones
Press the ZONES button for quick access to zones programming menus.
See for details item 4.1.1. for zone settings and 4.1.2. for zones grid view mode.
4.2.7.2. Loop Devices
Press the LOOP DEVICES button for quick access to loop devices programming menus.
See for details item 4.1.3. for device settings and 4.1.4. for devices grid view mode.
The sounder outputs will be activated together with the
LED TEST on the control panel and the icon indication on
the screen. No messages for events are generated.
To stop the test, press OFF button.
Quick summery of the submenus:
- Quick access to ZONES programming menu
- Quick access to DEVICES programming menu
- Grid view of attached devices to zone and loop
number
- Menu for disabling/enabling the operation of the
panel's outputs.
- Quick grid view of zones (by number) and loop
devices (by address) operation status