Main Functional Buttons; Sound Signalization - Teletek electronics iRIS8 User Operation & Maintenance Manual

Addressable fire alarm control panel
Hide thumbs Also See for iRIS8:
Table of Contents

Advertisement

The messages for Test and Warning events are with the lowest priority. The list with the events is not displayed
automatically and the user has to press the respective button to review them. The list is in grey color.
Reviewing the list with Test type events.
To exit to the main screen press, EXIT or MENU functional buttons.
Attention: At Access Level 1, and active events for Faults and/or Disablements, the iRIS8 panel always will
switch on from Main Screen to the messages list automatically after 20 seconds.
At Access Level 2 and Access Level 3 the iRIS8 panel will switch on to the messages list only in case of new
events for Alarm, Fault or Disablement.

2.3.3. Main Functional Buttons

The action of the functional buttons is common at all Access Levels and programming menus.
Button
Color
blue
blue
blue
grey

2.4. Sound Signalization

The iRIS8 fire alarm panel is equipped with internal buzzer for sound signalization in case of events.
Signalization
Button
Single short beep indicating the pressing of a button.
Single long beep indicating reset of the panel, receiving of message for Disable, Test or Warning
Reset or Event
event, successful activation of zone in test mode.
Short beeps in case of receiving of messages for Fault event (for the panel itself or for other fire
alarm panels in the network). The beeps can be stopped from Access Level 2 and 3 after
performing Silencing Buzzer* – see item 3.2.1.
Technical trouble
The beeps will stop when the technical trouble is restored and the fault event is cleared
automatically from the Faults list.
Continuous sound for activated Fire Alarm from zone or Evacuation. The sound can be stopped
Fire Alarm
from Access Level 2 and 3 after performing Silencing Buzzer* – see item 3.2.1.
* Note: The Buzzer Sound signalization of iRIS8 panel can be silenced from all other panels connected in the network.
The Buzzer Sound signalization of iRIS8 itself can be enabled or disabled for operation from the installer's programming
menus only!
iRIS8 - Addressable Fire Alarm Panel – User & Maintenance Manual
State
Active
Button for changing the User Access Level.
Active
Quick button for return to Main Screen.
Active
Step back in programming menus. Cancelling the introduced changes.
Not active
Idle button, with no function.
Reviewing the list with Warning type events.
Description
Description
13