Trouble Events - Teletek electronics ECLIPSE 8 Installation Manual

Alarm control panel
Hide thumbs Also See for ECLIPSE 8:
Table of Contents

Advertisement

Eclipse 8/16/32/99 Series - Installation Manual

4. TROUBLE EVENTS

The possible system troubles are listed in the table below as the indication differs according the type of the used
keyboard:
- Keyboard LED 8 – The troubles are displayed with a lighting zone LED or lighting up digit button.
- Keyboards LED 32 and LED 16A – The troubles are displayed with a lighting zone LED.
- Keyboards LCD 32 and LCD 32 Sensitive – The troubles are displayed as text messages.
The sound signalization for a system trouble (two short sound signals at every 20 seconds) can be disabled/enabled in
Menu 2. SETTINGS – 03. TRBL SOUNDS (ADDRESS 0013 or OPERATION 013). The signalization is common for all
troubles. By default, the sound signalization for all system troubles is enabled.
LED 32/
LED 8
LED 16A
Button "1"
Button "2"
Button "3"
Button "4"
* It is possible, after the initial power-up of ECLIPSE 32 or ECLIPSE 99 panel, a trouble message for 8.SOUNDER
FAULT to be displayed on the screen of LCD keyboards (8 zone number lights on the LED display). That indicates
some problems with sounder connected to PGM5. In case the monitored PGM is used as a standard output, you have
to terminate it with 1K resistor, or to program it as regular output – disable option 1 at ADDRESS 3051.
** The message is displayed at the initial power-up of the panel and after every hardware reset of the system. The
installer must set the actual time to clear the trouble message.
LCD 32/
LCD 32 Sensitive
1. AC Loss
The mains power supply is lost.
The accumulator battery is discharged or
2. Battery Trouble
missing.
3. Blown fuse
Blown out fuse.
Telephone line (PSTN) or digital
communicator (GPRS) is lost. Communication
4. Comm. TRBL
with central Monitoring station fails.
Sending of message (PSTN/GPRS/LAN) is
impossible.
5. Tamper
Open tamper in the system.
System bus error. It could be short circuit in
6. Sysbus err
the line or lost device.
7. Fire line Error
Fire Detector Loss or the fire line is broken.
Problem with a connected siren; no siren
8. Siren Fault*
connected to PGM5 (ECLIPSE 32/99).
The internal clock has to be set to an actual
9. Invalid clock**
time and date.
Possible problems:
10. WL device
- Low battery charge of wireless device;
trouble.
- Wireless device lost;
- Dirty chamber of a wireless fire detector.
11. WL RF
Radio signal jamming.
jamming.
Possible problems with power supply of
expander modules:
12. AUX PSU
- The mains power supply is lost;
trouble.
- Problem with the backup battery;
- Blown out fuse.
Description
32
Control panels Eclipse
8
16
32
99