Led Indication For Activated Zones - Teletek electronics iRIS8 User Operation & Maintenance Manual

Addressable fire alarm control panel
Hide thumbs Also See for iRIS8:
Table of Contents

Advertisement

iRIS8 - Addressable Fire Alarm Panel – User & Maintenance Manual

2.2. LED Indication for Activated Zones

The LED indication for activated zones is available on the front panel for zone numbers from 1 to 200. The zone number
is lighting or blinking according the type of the generated fire alarm together with the status LEDs of the panel.
GENERAL FIRE ALARM
One or several zones can be in alarm mode after fire or
evacuation event in the system. The numbers of activated
zones are lighting on in red together with the GENERAL
FIRE system status LED.
The indication will stay active even when the sounders are
silenced. The indication is cleared automatically after
resetting the panel and restoring the normal operation mode
of the zones – see item 3.2.3.
On the TFT screen is displayed detailed information about
the fire alarm event(s) – see item 2.3.2.
PRE ALARM Condition
The pre-alarm condition is applied for zones set in 2Devices
or DOUBLE operation mode. The numbers of activated
zones are blinking in red and the PRE ALARM and
WARNING system status LEDs are lighting on.
The indication is cleared automatically after resetting the
panel and restoring the normal operation mode of the zones
– see item 3.2.3.
On the TFT screen is displayed detailed information about
the pre-alarm and warning event – see item 2.3.2.
TEST Condition
Testing of the zones is possible from Access Levels 2 and 3.
The system status LED TEST is lighting on. In case of
activation of zone in test mode, its number is lighting on in
red. There is no indication for general fire or pre-alarm event.
The indication is cleared automatically after resetting the
tested device and stopping the zone test.
On the TFT screen is displayed detailed information about
the zone test – see item 2.3.2.
Performing of zone testing is described in details in item
4.2.6.1.
Note: The disabled for operation zones do not report for fire, faults, evacuation or test events. If DISABLE system status
LED is lighting on, you can review the type of the disablements (including zones disablements) in Events Reviewing
mode on the TFT screen.
The LED indication for zones can be tested for operation at Access Level 2/3 in Maintenance menus – see item 4.2.6.2.
8