Teletek electronics iRIS8 User Operation & Maintenance Manual page 27

Addressable fire alarm control panel
Hide thumbs Also See for iRIS8:
Table of Contents

Advertisement

Selected zone numbers are presented with black digit on
dark grey button. Next pressing of selected zone number
deselects it.
Press TEST button to start testing of the selected zone
numbers.
Go to the zone site and test the devices for operation.
The successful test is confirmed with a text message on
the screen "TEST ALARM" at alarm events list and single
long sound from the panel's buzzer.
The number of the tested zone is lighting on the front
panel.
Reset the activated device to normal operation mode.
Continue in the same way testing the other devices
attached to that zone.
After finishing with zone testing, it is recommended to reset the panel from the main screen – press MENU and then
RESET button.
4.2.6.2. Indication Test
The indication test allows the user to review the correct operation of the LED indication on the front panel and the
sound signal of the internal buzzer.
To perform the indication test, enter MAINTENANCE – TEST – INDICATION TEST. All LEDs on the front panel start
blinking and the internal buzzer is sounding. The panel will automatically exit the indication test mode after 5 seconds.
The colors of the system status indication LEDs are presented in item 2.1.
4.2.6.3. Device Test
This is a service menu for verification of communication between the panel and the devices connected to loop. The user
can select the loop and address number of a device and check the number of communication packets at "Yes/No" field.
The connection is reset with RESET button on the top.
iRIS8 - Addressable Fire Alarm Panel – User & Maintenance Manual
Single long sound from the panel's buzzer will inform for
stating zone tests. At events list are registered messages
for zone numbers in test mode.
Note: In test mode, the disabled for operation zones will
not send messages after activation. You can check if
there are disabled zones from the events list for
disablements or going to Programming menus – Zones
Grid View – see item 4.1.2.
Before stopping the running zone tests, first make
sure that all activated devices are reset to normal
operation mode.
Go back to SYSTEM – MAINTENANCE – TEST – ZONE
TEST and press STOP button.
The indication on the front panel will be cleared
automatically, as well the alarm events list.
Use EXIT button to return back to TEST Menus.
27