User Operation; Access Level 1 - Teletek electronics iRIS8 User Operation & Maintenance Manual

Addressable fire alarm control panel
Hide thumbs Also See for iRIS8:
Table of Contents

Advertisement

iRIS8 - Addressable Fire Alarm Panel – User & Maintenance Manual

3. USER OPERATION

In Operation section (see the screen in item 2), the User can perform different actions, according set Access Level –
see the table in item 1.4.
IMPORTANT NOTES for iRIS8 operation in a network:
The iRIS8 panel can perform SILENCE BUZZER, SILENCE ALARM, RESET and EVACUATE actions to
other panels in the network only when it is programmed (enabled) to send commands to them.
The iRIS8 panel can receive and display messages for events from other panels in the network only
when it is programmed (enabled) to receive commands from them.
Only panels enabled for receiving commands from other panels in the network will perform the sent
command.
The settings for Receiving and Sending commands are programmed at Installer's Access Level 3.

3.1. Access Level 1

At Access Level 1 the users can perform:
- Review events for the panel and the network – see the details in item 2.3.2.
- Silence Buzzer of the panel or other fire panels in the network – see the details in item 3.1.1.
- Evacuation Fire Alarm of the protected sites to all connected fire panels or some of them, when there is active
fire alarm signal received from a loop device – see the details in item 3.1.2.
The Main Screen at Access Level 1 and no active messages for events:
At Access Level 1 and active messages for Faults and/or Disablement events, the panel will always automatically
switch on from Main Screen to events list after 20 seconds.
You can return back to Main Screen pressing EXIT or MENU button. The panel will continue switching on to events list
until the faults/disablements are restored or user with Access Level 2 or 3 is logged in.
After 20 sec.
14