Start/Stop Operation Using the Power Supply
The SmartAXIS can be started and stopped by turning power on and off.
Power up the SmartAXIS to start operation.
1.
2.
Turn power on and off to start and stop operation.
Order of Powerup and Powerdown
To turn the power on, turn on the SmartAXIS and I/O sides at
the same time, or turn on the I/O side first, followed by the
SmartAXIS side.
To turn the power off, turn off the SmartAXIS and I/O sides at
the same time, or turn off the SmartAXIS side first, followed by
the I/O side.
Start/Stop Operation Using Stop Input and Reset Input
Any input terminal available on the SmartAXIS can be designated as a stop or reset input using the Function Area Settings. The
procedure for selecting stop and reset inputs is described "Stop Input and Reset Input" on page 5-4.
Note: When using a stop and/or reset input to start and stop operation, make sure that start control special internal relay M8000 is on. If M8000 is
off, the SmartAXIS does not start operation when the stop or reset input is turned off. M8000 is not turned on or off when the stop and/or reset
input is turned on or off.
When a stop or reset input is turned on during program operation, the SmartAXIS stops operation, and all outputs are turned off.
The reset input has priority over the stop input.
System Statuses at Stop, Reset, and Restart
The system statuses during running, stop, reset, and restart after stopping are listed below:
Mode
Output
Run
Operating
Stop
OFF
Restart
Unchanged
Reset
OFF
(Reset input ON)
Power OFF
OFF
4-20
Internal Relay, Shift
Register, Counter,
Data Register
Keep Type
Clear Type
Operating
Operating
Unchanged
Unchanged
OFF/
Unchanged
Reset to zero
OFF/
OFF/
Reset to zero
Reset to zero
Unchanged
Unchanged
S
A XI S P
/ L
U
M AR T
R O
I TE
SER
I/O Side Power
SmartAXIS Power
Special
Special Data
Internal
Register
Relay
Operating
Operating
See Chapter 7
Unchanged
Unchanged
Unchanged
Unchanged
Unchanged
See Chapter 7
Unchanged
'
M
FT9Y-B 1378
S
ANUAL
ON
OFF
ON
OFF
0 sec or more
0 sec or more
Non-
Timer
Maintained
Current
Data
Value
Register
Operating
Operating
Unchanged
Unchanged
Unchanged
Reset to preset
OFF/
Reset to zero
Reset to zero
OFF/
Reset to zero
Reset to zero