Download Print this page

IDEC HR1S-ATE Series Instructions

Safety relay modules
Hide thumbs Also See for HR1S-ATE Series:

Advertisement

Quick Links

HR1S-ATE Safety Relay Modules
New compact safety relay modules. Size is reduced by 50% from conventional models.
Plug-in terminal structure enables simple wiring.
EN ISO 13849-1 performance level e, safety category 4
compliant, and EN 62061 safety integrity level 3.
Integrated and removable teminal styles available.
Compact design: 45 mm in width.
Time delay outputs: 3NO
Auxiliary output enables power supply monitoring, inputs
(2 channels), and a time delay output.
Environmentally friendly, RoHs directive compliant.
UL Listed, CSA certified,
TÜV NORD approved.
Type
Type No.
HR1S-ATE5110
Integrated Terminal Block
HR1S-ATE5110P
Removable Terminal Block
Specifications
EN 60204-1: 2007
EN 60947-1: 2007
EN 60947-5-1:2004
EN 61000-6-2: 2005
Applicable Standards
EN 61000-6-4: 2007
EN 62061: 2005
EN ISO 13849-1: 2008
EN ISO 13849-2: 2008
Applicable Standards
EN 60204-1: 2006
for Use
EN ISO 13850: 2008
Performance level (PL)
e (EN ISO 13849-1)
Safety Category
4 (EN ISO 13849-1)
Safety Integrity Level (SIL)
3 (EN 62061)
Stop Category
0, 1 (EN 60204-1) (Note)
Operating Temperature
–10 to +55ºC (no freezing)
Relative Humidity
30 to 85% RH (no condensation)
Impulse Withstand Voltage
4 kV (IEC 60947-5-1)
Shock Resistance
150 m/s
10 to 60 Hz, amplitude 0.35 mm
Vibration Resistance
60 to 150 Hz, acceleration 50 m/s
Degree of Protection
Terminal: IP20 Enclosure: IP40
24V AC –20% +10%
Rated Voltage
24V DC –20% +20%
Power Consumption
24V AC: 8 VA max. 24V DC: 4W max.
Overcurrent Protection
Built-in, electronic
Minimal Applicable Load
17V DC / 10 mA (initial value)
Response Time
ON→OFF: 20 ms max. (instantaneous output)
Overvoltage Category
III
Pollution Degree
2
Rated Insulation Voltage
300V AC
Safety Circuit
2NO
Time-delay Circuit
3NO
Contact
None
Auxiliary
Circuit
Transistor
4
AC15
C300 (230V AC / Ie=0.75A)
Safety
Circuit
DC13
24V DC / Ie=1A
AC15
C300 (230V AC/ Ie=0.75A)
Time-
delay
DC13
24V DC / Ie=1A
Circuit
Preset Time
0, 0.5, 1, 2, 4, 6, 8, 10, 15, 20, 25, 30 sec.
Auxiliary Circuit
24V DC / 20 mA (PNP)
Mechanical Durability
10,000,000 operations
Electrical Durability
See page 4
Rated Current
Total output: 8A max. 1 output 4A max.
2
Package Quantity: 1
Terminal Style
, 11m sec, 3 shocks in each 3 axes
2
2
Single wire: 0.2 to 2.5 mm
HR1S-ATE5110
Multiple wires: 0.14 to 0.75 mm
Wire Size
HR1S-
Single wire: 0.2 to 2.5 mm
ATE5110P
Multiple wires: 0.2 to 1.5 mm
Weight (approx.)
280g
Note: Safety output contact
Stop category 0
Time-delay output contact
Stop category 1
Use a 4A fuse (Type gG) for power protection.Use a 6A fuse (Type gG)
for safety output protection. Use a 4A fuse (Type gG) for time-delay output
and auxiliary output protection.
Dimensions
HR1S-ATE5110 Integrated Terminal Type
114
HR1S-ATE5110P Removable Terminal Type
114
LED Indicator
A1/A2 Fuse: Turns on when power circuit is normal.
Input A S12: Turns on when S11–S12 is closed.
A1/A2
Fuse
Input B S22: Turns on when S21–S22 is closed.
Input A
Stop1:
S12
Input B
S22
Stop 1
max. (24~14 AWG)
2
max.
2
max.(24~14 AWG)
2
max.
2
45
45
All dimensions in mm.
Turns on when the time-delay output
circuits 57-58, 67-68, and 77-78 are
closed.
(100705)

Advertisement

loading

Summary of Contents for IDEC HR1S-ATE Series

  • Page 1 HR1S-ATE Safety Relay Modules New compact safety relay modules. Size is reduced by 50% from conventional models. Plug-in terminal structure enables simple wiring. EN ISO 13849-1 performance level e, safety category 4 • compliant, and EN 62061 safety integrity level 3. Integrated and removable teminal styles available.
  • Page 2 HR1S-ATE Safety Relay Modules HR1S-ATE Wiring Diagram Safety category is achieved by an entire control system. Take the connected safety equipment and wiring into consideration. Safety Category 4 (3) Circuit • (using an emergency stop switch) (Note) When not monitoring the start switch •...
  • Page 3 Tel: +86-755-8356-2977 E-mail: opencontact@idec.com IDEC ELEKTROTECHNIK GmbH IDEC IZUMI (H.K.) CO., LTD. IDEC CANADA LIMITED Tel: +49-40-25 30 54 - 0 E-mail: service@idec.de Tel: +852-2803-8989 E-mail: info@hk.idec.com Tel: +1-905-890-8561, Toll Free: (888) 317-4332 IDEC (SHANGHAI) CORPORATION IDEC TAIWAN CORPORATION E-mail: sales@ca.idec.com Tel: +86-21-5353-1000 E-mail: idec@cn.idec.com...

This manual is also suitable for:

Hr1s-ate5110Hr1s-ate5110p