5: S
F
P ECI AL
UN CTI ON S

Frequency Measurement

This section describes frequency measurement, which measures the frequency of pulses input to an external input. Frequency
measurement is a function that measures the frequency of pulses input to an external input.
These input pulses are processed with dedicated hardware device in SmartAXIS, so frequencies can be measured with no relation
to the scan time. Groups that do not use frequency measurement can be used as normal inputs, high-speed counters, catch input,
and interrupt input. The measurement results are stored in special data registers and they are updated with each scan.
Function Specification
The SmartAXIS external inputs are used by switching between normal input, high-speed counters, catch input, interrupt input, and
frequency measurement. To use frequency measurement, specify the relevant group as Frequency Measurement in the
WindLDR Function Area Settings.
The frequency measurement results are stored in the following special data registers (Read-only):
Group
External input
Frequency measurement
value (32 bits)
Frequency measurement range
Measurement error
Calculation cycle
Notes:
If the input pulse cycle is longer than the scan time, the measurement results are updated at pulse cycle + 1 scan time.
The data registers for the upper word and the lower word of the measurement value change according to the 32-bit data storage method
specified. For details, see "32-bit Data Storage Setting" on page 5-62.
Applicable Models
The AC power type does not support frequency measurement. In situations where the frequency measurement function is required, use the
DC power type.
Of the DC power types, only the the 24-, 40-, and 48-I/O types can use external inputs I6 and I7 for frequency measurement. The 12-I/O
type cannot use external inputs I6 and I7 as the frequency measurement function.
5-36
1
I0
Upper word
D8050
Lower word
D8051
1 Hz to 100 kHz
S
A XI S P
/ L
M AR T
R O
2
3
I2
I3
D8056
D8062
D8057
D8063
Less than ±1%
(Truncated after the decimal point)
Each scan time
U
'
M
FT9Y-B 1378
I TE
SER
S
ANUAL
4
5
I5
I6
D8068
D8134
D8069
D8135
200 Hz to 100 kHz
6
I7
D8140
D8141