User Communication Server

When a server connection is configured as the user communication server, a client device can access and communicate with the
SmartAXIS. The SmartAXIS communicates with the client device according to the settings configured in the ETXD and ERXD
instructions that are programmed for the server connection. The local host number and other communication settings can be
configured in the Connection Settings tab in the Function Area Settings dialog box.
Specifications (User Communication Server)
Item
Local host port number
Number of clients that can simultaneously
communicate with the SmartAXIS
Receive timeout
Note 1: A maximum of three connections can be allocated to user communication servers, and a maximum of three client devices can
simultaneously connect to and communicate with the SmartAXIS.
Note 2: The receive timeout is enabled when using the ERXD instruction. To disable the receive timeout, set it to 25500 ms.
User Communication Server Receive Instruction (ERXD) Cancel Flag
The allocation of the user communication receive instruction cancel flags for each server connection is shown in the table below.
For details about the user communication receive instruction cancel flag, see Chapter 25 "User Communication Instructions" in the
SmartAXIS Ladder Programming Manual.
Device Address
M8100
M8101
M8102
2102 to 2104 (Can be changed between 0 and 65535)
One client per a user communication server (Note 1)
100 to 25400 ms (100 ms increments) (Note 2)
User Communication Receive Instruction Cancel Flag (Connection 1)
User Communication Receive Instruction Cancel Flag (Connection 2)
User Communication Receive Instruction Cancel Flag (Connection 3)
S
A XI S P
/ L
M AR T
R O
10 : U
User Communication Server
Description
U
'
M
FT9Y-B 1378
I TE
SER
S
ANUAL
C
SER
OM M UN I CATI ON
I
N STR UCTI ON S
10-19

Advertisement

Table of Contents
loading

Table of Contents