Forced I/O function

Inputs can be forced on/off regardless of the status of physical inputs, and outputs can be forced on/off regardless of the ladder
logic using the forced I/O function in WindLDR. The force input function can be used to monitor or online edit mode to test the
ladder logic without the need of wiring the input terminals or turning on the actual inputs. The force output function can be used
to turn on/off the outputs to the external devices.
The forced I/O may cause unexpected operation of the SmartAXIS. Make sure of safety before forcing inputs or
Caution
outputs.
Devices
All the inputs and outputs of the SmartAXIS can be forced on/off individually.
Type
12-I/O type
I0 to I7
24-I/O type
I0 to I17, I40 to I75, I80 to I115, I120 to I155
40-I/O type
I0 to I27, I40 to I75, I80 to I115, I120 to I155
48-I/O type
I0 to I35, I40 to I75, I80 to I115, I120 to I155
Forced I/O Status
Events of the SmartAXIS and effects on the forced I/O settings are shown below.
When the SmartAXIS starts running
When the SmartAXIS is stopped.
When the SmartAXIS is powered up
When user program download is executed
When Reset Input is turned on
When Clear All Devices is executed in the PLC Status dialog
box of WindLDR
When the system software download is executed
Note: Force function has no effect on high-speed counters, catch inputs, or interrupt inputs. The stop or reset input can be initiated using the force
function, but the force settings will be cleared as soon as the reset input is turned on.
Checking the Forced I/O Function Execution State
The state of the forced I/O function (running or stopped) can be checked with WindLDR, with the SmartAXIS module error status
LED (SmartAXIS Lite only), or with the RUN or STOP screen on the module's LCD (SmartAXIS Pro only). The forced I/O function
execution state while stopped cannot be checked with the module's power/run status LED. For the power/run status LED, see
"Product Specifications" on page 2-1.
Inputs
Events
S
A XI S P
M AR T
Device Range
Q0 to Q3
Q0 to Q7, Q40 to Q61, Q80 to Q101, Q120 to Q141
Q0 to Q17, Q40 to Q61, Q80 to Q101, Q120 to Q141
Q0 to Q21, Q40 to Q61, Q80 to Q101, Q120 to Q141
The force settings are retained. The forced inputs and outputs are kept on/off
even after the SmartAXIS is stopped, regardless of the status of M8025
(maintain outputs while SmartAXIS is stopped).
The force settings are retained, but the force is suspended. If the battery is
dead, the force settings are cleared.
The force settings are retained, and whether the force will be suspended or
not can be selected in the Download Program dialog box.
The force settings are cleared.
/ L
U
'
M
FT9Y-B 1378
R O
I TE
SER
S
ANUAL
5: S
P ECI AL
Outputs
Forced I/O Status
F
UN CTI ON S
5-43