LED Display for Viewing Status at a Glance
The LED indicators display approximately 20 different states by steady or flash light, or by combining. (For details, see page 28.)
When an error occurs, its location is indicated, allowing maintenance to be performed immediately.
ERROR does not light on.
Indicates that safety-related
input is activated.

Delay Function

By using the dials to set a combination of a coefficient from 0 to
0.9 and a magnification from 1x to 1000x, time limit can be set
in the range of 0 to 900 seconds.
Also, the external input can be used to cancel the off-delay and
immediately cut off the output. Expanded (*1) output can be set
to either instantaneous or delay.
6
ERROR flashes, and S12 and
S22 flash alternately.
Flash
Indicates a safety input
synchronization alert.
*1: Expansion output is set to
instantaneous for 1 to 4, and to
delay output for 5 to 8.
ERROR is steady, and either S12
or S22 flashes. If both flash, the
flashing synchronizes.
Flashes
alternately
Flash
Indicates a cross circuit in a
safety input.
Screw or Push-in
Terminal Block
Choose from two types: a conventional screw terminal block or
a highly-reliable push-in terminal block that saves wiring time.
Both are removable and easy to maintain.
Push-in terminal
All LEDs light on.
Indicates that an inappropriate
function mode has been set,
or a setting has been changed
after power on.
Screw terminal