Parameter
(Digital) Activation
Delay
((DIG) ACTIVATION
DELAY)
(FLS) Low Fuel Level
Shutdown
(SHUTDOWN)
(FLS) Shutdown
Threshold
(SHUTDOWN
THRESHOLD)
(FLS) Low Fuel Level
Warning
(WARNING)
(FLS) Warning
Threshold
(WARNING
THRESHOLD)
(FLS) Fuel Tank
Capacity
(FUEL TANK SIZE)
(FLS) Fuel Theft
Warning
(FUEL THEFT ALARM)
(FLS) Fuel Theft Alarm
Threshold
(FUEL LVL THRESH)
(FLS) Circuit Fault
Action
(OPEN CKT ALARM)
(FLS) Fuel Sensor
Reference
(FUEL LVL REF)
(FLS) Fuel Level
Sensor Calibration
Table
Analogue Input 3 (LOP / DIG F)
Parameter
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
User manual 4189341354A EN
Range
From Monitoring On
Always
1 to 60 s
Enable
Disable
0 to 78 %
Enable
Disable
2 to 80 %
2 to 1000 litre
Enable
Disable
1 to 100 % per hour
None
Notification
Warning
Electrical Trip
Shutdown
Battery Negative
Engine Body
Resistance: 0 to 1000
Ω
Fuel level: 0 to 100 %
Range
Not used
Digital Input F
Lube Oil Pressure
See Digital input
source selection in
this document
Default
1 s
Not enabled
10 %
Enabled
12 %
100 litre
Enabled
50 %
None
Engine Body
-
Default
Not used
Not used
Description
If the input is active when the timer expires, the
controller actives the action for the digital input.
If this parameter is enabled, the controller shuts
down the engine when the fuel level is less than
the shutdown set point (SHUTDOWN
THRESHOLD).
The controller shuts down the engine when the
fuel level is less than this set point.
If this parameter is enabled, the controller
shows a notification when the fuel level is less
than the notification set point (NOTIFICATION
THRESHOLD).
The controller shows a notification when the
fuel level is less than this set point.
Configure the fuel tank capacity.
If this parameter is enabled, the controller
activates an alarm when the fuel level is less
than the set point for the fuel theft alarm.
If the fuel consumption per hour is more than
this set point, the controller activates an alarm.
The percentage is of the nominal fuel
consumption.
Configure the action for when there is an open
circuit failure.
Select the reference point for the fuel sensor.
Configure the resistance and fuel level values
for the 10 measurement points in the calibration
table.
Description
Select what to use the input as.
Select the source from the list.
Page 24 of 72