Deif SGC 121 User Manual page 37

Single genset controller
Hide thumbs Also See for SGC 121:
Table of Contents

Advertisement

Parameter
Automatic Fuel Transfer (AFT FUNCTION)
Parameter
AFT Activation
Threshold
(AFT ACT
THRESHOLD)
AFT deactivation
threshold
(AFT DEACT
THRESHOLD)
Timeout After
Activation
(TIMEOUT AFTER ACT)
Monitor AFT From
Engine On (MON AFT
ON ENG ON)
Engine Coolant Temperature
Parameter
Shutdown
Shutdown Threshold
Warning
Warning Threshold
Temp. Threshold Type
Lube Oil Pressure (LOP)
Parameter
Low Level Shutdown
Shutdown Threshold
Low Level Warning
User manual 4189341354A EN
Range
Range
0 to 99 %
1 to 100 %
1 to 1200 s
Enable
Disable
Range
Enable
Disable
27 to 300 °C
Enable
Disable
25 to 298 °C
Greater Than
Threshold
Less Than Threshold
Range
Enable
Disable
0.0 to 9.8 Bar
Enable
Disable
Default
Default
40 %
80 %
600 s
Not enabled
Default
Not enabled
27 °C
Not enabled
25 °C
Greater Than
Threshold
Default
Not enabled
2 Bar
Not enabled
Description
Heater control: If the heater temperature is
more than the OFF threshold, the output for
Coolant Temperature Control is deactivated.
Description
If the fuel level is less than this threshold, the
auto fuel transfer output is activated.
If the fuel level is more than this threshold, the
output for auto fuel transfer is deactivated.
If the fuel level is less than the deactivation
threshold when this timer expires, the controller
activates a timeout alarm and deactivates the
fuel transfer output.
If this parameter is enabled, the controller
monitors the fuel level when the engine is
running.
Description
If this parameter is enabled, the controller shuts
down the engine when the temperature is more
than the shutdown set point (Shutdown
Threshold).
If the engine temperature is more than this set
point, the controller shuts down the engine.
If this parameter is enabled, the controller
activates a warning alarm when the
temperature is more than the warning set point
(Warning Threshold).
If the engine temperature is more than this set
point, the controller activates a warning alarm.
Configure if the controller activates a shutdown
and/or a warning when the monitored value is
less than or more than the set points.
Description
If this parameter is enabled, the controller shuts
down the engine when the lube oil pressure is
less than the shutdown set point (Shutdown
Threshold).
If the lube oil pressure is less than this set
point, the controller shuts down the engine.
If this parameter is enabled, the controller
activates a warning alarm when the lube oil
Page 37 of 72