Deif SGC 121 User Manual page 31

Single genset controller
Hide thumbs Also See for SGC 121:
Table of Contents

Advertisement

Parameter
(OF WARNING
THRESHOLD)
Over-frequency
Warning Delay (OF
WARNING DELAY)
Current Monitoring (CURRENT MONITOR)
Parameter
CT Ratio
(LOAD CT RATIO)
Over-current Action
(OVER CURR ACTION)
Over-current
Threshold
(OVER CURR
THRESHOLD)
Over-current Delay
(OVER CURR DELAY)
CT Location
(CT LOCATION)
Load Monitoring (LOAD MONITOR)
Parameter
Overload Action
(OVERLOAD ACTION)
Overload Threshold
(OVERLOAD
THRESHOLD)
Overload Monitoring
Delay
(OVERLOAD MON
DELAY)
Unbalanced Load
Action
(UNBAL LOAD
ACTION)
Unbalanced Load
Threshold
(UNBAL LOAD
THRESHOLD)
User manual 4189341354A EN
Range
0.1 to 100 s
Range
0 to 8000 / 5
None
Notification
Warning
Electrical Trip
Shutdown
5 to 10000 A
1 to 600 s
On Alt Output Cable
On Load Cable
Range
None
Notification
Warning
Electrical Trip
Shutdown
50 to 150 %
1 to 600 s
None
Warning
Electrical Trip
Shutdown
Notification
5 to 200 %
Default
10 s
Default
150/5
None
120
1 s
On Alt Output Cable
Default
None
90 %
1 s
None
5 %
Description
If the frequency is more than the set point for
over-frequency warning (OF WARNING
THRESH) when this timer expires, the controller
shuts down the engine.
Description
CT ratio.
Configure the action for when over-current is
detected.
The action for over-current is activated when
the current is more than this set point.
When the delay timer expires, the action for
over-current is activated if the current is more
than over-current set point.
Configure the location of the CT. You can place
the CT on the line from the genset or on the
load cable.
Description
The action that occurs when the load is more
than the overload set point.
The action for overload is activated when the
load is more than this set point.
When the delay timer expires, the action for
overload is activated if the load is more than
the overload set point.
The action that occurs when the load is more
than the unbalanced load set point.
The action for unbalanced load is activated
when the load is more than this set point.
Page 31 of 72