Parameter
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation
Delay
((DIG) ACTIVATION
DELAY)
(ETS) Circuit Fault
Action
(OPEN CKT ALARM)
(ETS) Engine
Temperature Sensor
Calibration Table
Analogue Input 2 (FUEL LVL / DIG H)
Parameter
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
User manual 4189341354A EN
Range
Engine Coolant
Temperature Sensor
See Digital input
source selection in
this document
Auxiliary Input G
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 60 s
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 0 to 1000
Ω
Temperature: 25 to
300 °C
Range
Not used
Digital Input H
Fuel Level Sensor
See Digital input
source selection in
this document
Auxiliary Input H
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
Default
Not used
-
Close to Activate
None
From Monitoring On
1 s
None
-
Default
Not used
Not used
-
Close to Activate
None
From Monitoring On
Description
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
Configure the action for when there is a circuit
failure.
Configure the resistance and temperature
values for 10 measurement points in the
calibration table.
Description
Select what to use the input as.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
Page 23 of 72