5. General functions

5.1

AC measurement systems

The AC system can be three-phase, two-phase, single-phase, or split phase.
Incorrect configuration is dangerous
Configure the correct AC configuration. If in doubt, contact the switchboard manufacturer for information.
5.2

Nominal settings

5.2.1

Default nominal settings

Text
Nominal voltage (phase-
neutral)
Nominal voltage (phase-
phase)
Nominal frequency
Nominal load current
Nominal 4th CT current
Nominal speed
Nominal power (kW)
5.2.2

Alternative nominal settings

Text
Nominal voltage (phase-
neutral)
Nominal voltage (phase-
phase)
Nominal frequency
User manual 4189341354A EN
Range
80 to 200000 V
80 to 40000 V
5 to 75 Hz
0 to 8000 A
0 to 8000 A
100 to 4000 RPM
10 to 8000 kW
Range
80 to 200000 V
80 to 40000 V
5 to 75 Hz
CAUTION
Default
Note
Check the minimum and maximum values the SGC
230 V
can read and display. Remember to include the
PT.
Check the minimum and maximum values the SGC
400 V
can read and display. Remember to include the
PT.
Check the minimum and maximum values the SGC
50 Hz
can read and display.
Check the minimum and maximum values the SGC
350 A
can read and display. Remember to include the
CT.
Check the minimum and maximum values the SGC
800 A
can read and display. Remember to include the
CT.
Check the minimum and maximum values the SGC
1500 RPM
can read and display.
Check the minimum and maximum values the SGC
200 kW
can read and display. Remember to include the
PT.
Default
Note
Check the minimum and maximum values the SGC
230 V
can read and display. Remember to include the
PT.
Check the minimum and maximum values the SGC
400 V
can read and display. Remember to include the
PT.
Check the minimum and maximum values the SGC
60 Hz
can read and display.
Page 47 of 72