Deif SGC 121 User Manual page 36

Single genset controller
Hide thumbs Also See for SGC 121:
Table of Contents

Advertisement

Parameter
High Battery Voltage
Threshold
(HIGH VOLT
THRESHOLD)
High Battery Voltage
Delay
(HIGH VOLT DELAY)
Charging Alternator Monitoring (CHARGE ALT MON)
Parameter
Charging Alternator
Fail Action
(FAIL ACTION)
Charging Alternator
Fail Threshold
(FAIL THRESHOLD)
Charging Alternator
Fail Delay
(FAIL DELAY)
Preheating (PREHEAT)
Parameter
Pre-heat Timer
(PREHEAT TIMER)
Engine Temperature
(ENG TEMP EN)
Engine Temperature
Threshold
(ENG TEMP LIMIT)
Coolant Control
Parameter
Enable (coolant
control)
Temperature Control
ON Threshold
OFF Threshold
User manual 4189341354A EN
Range
9.0 to 32.0 V
5 to 1800 s
Range
None
Notification
Warning
Electrical Trip
Shutdown
0.0 to 35.0 V
5 to 60 s
Range
1 to 900 s
Enable
Disable
10 to 300 °C
Range
Enable
Disable
Heater Control
Cooler Control
0 to 250 °C
0 to 250 °C
Default
15 V
30 s
Default
None
10.0 V
10 s
Default
10 s
Not enabled
25 °C
Default
Not enabled
Heater Control
50 °C
50 °C
Description
The action for high battery voltage is activated
when the voltage load is more than this set
point.
If the battery voltage is more than the set point
for high voltage (HIGH VOLT THRESHOLD)
when the timer expires, the controller activates
the action for high battery voltage.
Description
Configure the action for charging alternator
failure.
The action for charging alternator failure is
activated when the alternator voltage is more
than this set point.
If the alternator voltage is more than the set
point for high voltage (FAIL THRESHOLD) when
the timer expires, the controller activates the
action for charging alternator failure.
Description
When the pre-heat timer expires, the engine
starts to crank.
If this parameter is enabled, the pre-heat
output is deactivated when the engine coolant
temperature is more than the set point for the
coolant temperature (ENG TEMP LIMIT).
The set point for the engine coolant
temperature.
Description
Enable this parameter to configure the coolant
control.
Select the type of coolant control.
Cooler control: If the cooler temperature is
more than the ON threshold, the output for
Coolant Temperature Control is activated.
Heater control: If the heater temperature is less
than the ON threshold, the output for Coolant
Temperature Control is activated.
Cooler control: If the cooler temperature is less
than the OFF threshold, the output for Coolant
Temperature Control is deactivated.
Page 36 of 72