Parameter
Communication (RS485 COMM)
Level 2
Communication Mode
(COMM MODE)
Server ID
(MODBUS SLAVE ID)
Baud rate
(BAUDRATE)
Parity Bit
(PARITY)
Auto Exercise – Event 1 (AUTO EXERCISE – 1)
Level 2
Auto Exercise
(EVENT 1)
Event Occurrence
(EVENT OCCURENCE)
Event Day
(EVENT DAY)
Start Time
(START TIME)
Duration
(GEN ON DURATION)
Load Transfer
(LOAD TRANSFER)
User manual 4189341354A EN
Range
Range
None
Modbus
1 to 247
1200
2400
4800
9600
19200
38400
57600
115200
None
Even
Odd
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
00:00 to 23:59 hour
00 hr 01 min. to 99 hr
59 min.
Enable
Disable
Default
Default
None
2
9600 bps
None
Default
Not enabled
Daily
Runs every day
10:00 hour
10 hours, 10 minutes
Not enabled
Description
This is only when the engine is not in operation.
You can configure the adjustable timer with the
smart connect software in Timers > General
> Power Save Mode Delay
Description
Select the communication mode.
Select the server ID for Modbus.
Select the baud rate for the serial
communication.
Select the parity bit for the serial
communication.
Description
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Configure how often the sequences occur.
Configure the start date for the sequences.
Configure the start time for the sequences.
Configure for how long the genset operates
during the scheduled sequences.
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Page 21 of 72