Deif SGC 121 User Manual page 29

Single genset controller
Hide thumbs Also See for SGC 121:
Table of Contents

Advertisement

Parameter
Alternator Nominal
Speed
Alternator Nominal
Power
Voltage Monitoring (VOLT MONITOR)
Parameter
Under-voltage
Shutdown
(UNDER VOLT
SHUTDOWN)
Under-voltage
Shutdown Threshold
(UV SHUTDOWN
THRESH)
Under-voltage
Shutdown Delay (UV
SHUTDOWN DELAY)
Under-voltage Warning
(UNDER VOLT
WARNING)
Under-voltage Warning
Threshold
(UV WARNING
THRESHOLD)
Under-voltage Warning
Delay (UV WARNING
DELAY)
Over-voltage
Shutdown
(OVER VOLT
SHUTDOWN)
Over-voltage
Shutdown Threshold
(OV SHUTDOWN
THRESH)
Over-voltage
Shutdown Delay (OV
SHUTDOWN DELAY)
Over-voltage Warning
(OVER VOLT
WARNING)
Over-voltage Warning
Threshold
User manual 4189341354A EN
Range
100 to 4000 RPM
10 to 8000 kW
Range
Enable
Disable
50 to 295 V phase-
neutral
0.1 to 100 s
Enable
Disable
55 to 300 V phase-
neutral
0.1 to 100 s
Enable
Disable
105 to 350 V phase-
neutral
0.1 to 100 s
Enable
Disable
100 to 345 V phase-
neutral
Default
1800 RPM
200 kW
Default
Not enabled
80 V
10 s
Not enabled
Not enabled
10 s
Not enabled
120 V
10 s
Not enabled
110 V
Description
Configure the nominal value for the alternator
speed.
Configure the nominal value for the alternator
power.
Description
If this parameter is enabled, the controller shuts
down the engine when the voltage is less than
the configured set point for under-voltage.
When the voltage is less than this set point, the
controller shuts down the engine.
If the voltage is less than the set point for
under-voltage shutdown (UV SHUTDOWN
THRESH) when this timer expires, the controller
shuts down the engine.
If this parameter is enabled, the display shows
a warning when the voltage is less than the set
point for the under-voltage warning.
When the voltage is less than the set point, the
controller shows a warning message.
If the voltage is less than the set point for
under-voltage warning (UV WARNING THRESH)
when this timer expires, the controller activates
a warning alarm.
If this parameter is enabled, the controller shuts
down the engine when the voltage is more than
the configured set point for over-voltage.
When the voltage is more than the set point,
the engine shuts down.
If the voltage is more than the set point for
over-voltage shutdown (OV SHUTDOWN
THRESH) when this timer expires, the controller
shuts down the engine.
If this parameter is enabled, the controller
shows a warning message when the voltage is
more than the over-voltage set point (OV
WARNING THRESHOLD).
When the voltage is more than the set point,
the engine shows a warning message.
Page 29 of 72