6.2 Ambient Conditions, Ventilation and Mounting Position

Storage, Transport
Normal operation
Surrounding
temperature in operation
Humidity in operation
Site altitude
Pollution level
Vibration
Shock
Drive protection
Drive EMC immunity
Mounting
Ventilation
(➜ # 23)
Environmental class 3K3 according to IEC 61800-2
Internal regen resistor used:
0 to +40 °C under rated conditions
l
+40 to +60 °C with output current derating 3 % per Kelvin
l
Internal regen resistor not used:
0 to +50 °C under rated conditions
l
+50 to +60 °C with output current derating 2 % per Kelvin
l
Relative humidity 5 to 85%, no condensation, IEC 61800-2 class 3K3
Up to 1,000 m AMSL (above mean sea level): no restriction
l
1,000 to 2,000 m AMSL: power derating 1.5%/100 m
l
Maximum altitude: 2,000 m AMSL
l
Pollution level 2 as per IEC 60664-1
Class 3M1 according to IEC 61800-2
Class L according to IEC 61800-2
IP 20 according to IEC 60529
Increased immunity according to EN 61800-5-2
Vertical position, in a cabinet with protection of at least IP 54
Minimum cabinet size (WxHxD): 406 x 406 x 254 mm
Built-in fan in all drive variants
The drive shuts down in case of excessively high temperature in the control cabinet. Make sure
sufficient forced ventilation is supplied within the control cabinet.