8.6.3 Auxiliary voltage power supply connector X10

The following diagram describes external 24 VDC power supply (PELV). The required supply current rating depends
on the use of motor brake (➜ # 35) or (➜ # 35).
Pin
Signal
1
+ 24 V
+24 VDC supply voltage, PELV
2
GND
Ground for 24 VDC supply voltage, PELV
For control supply current requirement specifications see section (➜ # 39).

8.6.3.1 Fusing

Use 24 VDC supply manufacturer's recommendation for fusing.

8.6.3.2 Wiring example 24 VDC supply

Maximum current for one string of daisy-chained X10T connectors is 20 A. The sum of the control currents of the
connected drives should not exceed 20 A. With the data given in the table above, you can connect for example:
6 single axis drives, or 4 dual axis drives, or 3 single + 2 dual axis drives.
Wiring example with three phase power supply unit:
2 pin, pitch 5.08 mm
l
T-type mating connector data (➜ # 54)
l
Undervoltage fault limit 19 V
l
Overvoltage fault limit 30 V