6.5.3 Steady State Control Current per Brake Option

Auxiliary 24 VDC (±10%, check voltage drop) Supply Voltage (PELV)
Base current for all AKD2G Sxx-xV 3-12 A drives with NO brake
Base current for an AKD2G Sxx-7V24S drive with NO brake
Additional current load per brake (maximum 2 brakes)*
* To calculate current for a drive plus a brake, add base drive current plus the current value for each brake.
For example:
1. AKD2G-Sxx-6V06D with two brakes: Net 24 V current < 1 + 2•(1.8) = 4.6 A
2. AKD2G-Sxx-7V24S with one brake: Net 24 V current < 1.5 + 1.8 = 3.3 A
AKD2G-S Installation Manual, Safety 1
Units
Kollmorgen | kdn.kollmorgen.com | June, 2023
Current
A
< 1
A
< 1.5
A
< 1.8
39