Danfoss iC7 Series Operating Manual page 56

Functional extension options
Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

Functional Extension Options
Operating Guide
Default Value: 0.00
Unit: ms
P 9.4.2.6 T3 Live Zero Threshold Value
Description: Set the live zero threshold value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2
Live Zero Response".
Default Value: -10
Unit: -
P 9.4.2.7 T3 Live Zero Timeout Value
Description: Set the live zero timeout value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2
Live Zero Response".
Default Value: 0.0
Unit: s
P 9.4.2.8 T3 Temperature Sensor type
Description: Select which type of temperature sensor is connected to the terminal.
Default Value: 0 [No sensor]
Unit: -
The following are the selections for the parameter:
Selection number
0
1
2
3
4
5
6
7
10
11
12
7.6.2.3 Output T4 (Menu Index 9.4.3)
P 9.4.3.1 T4 Terminal Mode
Description: Select the mode for the terminal.
Default Value: 0 [Inactive]
Unit: -
The following are the selections for the parameter
56 | Danfoss A/S © 2023.06
Parameter Type: Range (0.00 — 60000.00)
Data Type: REAL
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (0.0 — 60.0)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
Parameter Type: Selection
Data Type: UINT
General Purpose I/O Installation
Parameter Number: 4929
Access Type: Read/Write
Parameter Number: 4930
Access Type: Read/Write
Parameter Number: 4931
Access Type: Read/Write
Parameter Number: 4932
Access Type: Read/Write
Selection name
No sensor
Pt100
2xPt100
3xPt100
Pt1000
Ni1000Tk5000
Ni1000Tk6180
KTY84-1x0
KTY81/82-1x0
KTY81/82-121
KTY81/82-122
Parameter Number: 4045
Access Type: Read/Write
AQ390830267692en-000601 / 136R0273
and Configuration