Illustration 11: Wiring Configuration for Resolver and Incremental (TTL) Encoder
1
Resolver
2
External power supply
5.5.6 SinCos Encoder
Table 13: Parameters for SinCos Encoder
Parameter
9.4.1 Interface configuration
9.4.4 Encoder Supply Voltage
9.5.1 Resolution Device 1
24 | Danfoss A/S © 2023.06
Ref+
Ref–
Sin+
Sin–
Cos
Cos–
Setting
Select [10] SinCos A,B.
Set the appropriate supply voltage.
Voltage can be up to 24 V. Setting the voltage too high can damage the connected encoder.
Set the resolution of the encoder in pulses per revolution.
1
3
Incremental encoder (only TTL on Z and D)
N O T I C E
Encoder/Resolver Installation and
Configuration
2
3
A+
A–
B+