Danfoss iC7 Series Operating Manual page 24

Functional extension options
Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

Functional Extension Options
Operating Guide
17
15
9
7
3
5
2
1
18
16
14
12
10
8
6
4
13
11
Illustration 11: Wiring Configuration for Resolver and Incremental (TTL) Encoder
1
Resolver
2
External power supply
5.5.6 SinCos Encoder
Table 13: Parameters for SinCos Encoder
Parameter
9.4.1 Interface configuration
9.4.4 Encoder Supply Voltage
9.5.1 Resolution Device 1
24 | Danfoss A/S © 2023.06
Ref+
Ref–
Sin+
Sin–
Cos
Cos–
Setting
Select [10] SinCos A,B.
Set the appropriate supply voltage.
Voltage can be up to 24 V. Setting the voltage too high can damage the connected encoder.
Set the resolution of the encoder in pulses per revolution.
1
3
Incremental encoder (only TTL on Z and D)
N O T I C E
Encoder/Resolver Installation and
Configuration
2
3
A+
A–
B+
B–
AQ390830267692en-000601 / 136R0273

Advertisement

Table of Contents
loading

Table of Contents