Danfoss iC7 Series Operating Manual page 54

Functional extension options
Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

Functional Extension Options
Operating Guide
Selection number
1
2
P 9.4.1.3 T2 Minimum Value
Description: Set the voltage or current representing 0% of the signal.
Default Value: 0
Unit: -
P 9.4.1.4 T2 Maximum Value
Description: Set the voltage or current representing 100% of the signal.
Default Value: 10
Unit: -
P 9.4.1.5 T2 Filter Time
Description: Set the filter time for the terminal.
Default Value: 0.00
Unit: ms
P 9.4.1.6 T2 Live Zero Threshold Value
Description: Set the live zero threshold value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2
Live Zero Response".
Default Value: -10
Unit: -
P 9.4.1.7 T2 Live Zero Timeout Value
Description: Set the live zero timeout value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2
Live Zero Response".
Default Value: 0.0
Unit: s
P 9.4.1.8 T2 Temperature Sensor type
Description: Select which type of temperature sensor is connected to the terminal.
Default Value: 0 [No sensor]
Unit: -
The following are the selections for the parameter
Selection number
0
1
2
3
4
5
54 | Danfoss A/S © 2023.06
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (0.00 — 60000.00)
Data Type: REAL
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (0.0 — 60.0)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
General Purpose I/O Installation
Selection name
Voltage
Current
Parameter Number: 4917
Access Type: Read/Write
Parameter Number: 4918
Access Type: Read/Write
Parameter Number: 4919
Access Type: Read/Write
Parameter Number: 4920
Access Type: Read/Write
Parameter Number: 4921
Access Type: Read/Write
Parameter Number: 4922
Access Type: Read/Write
Selection name
No sensor
Pt100
2xPt100
3xPt100
Pt1000
Ni1000Tk5000
AQ390830267692en-000601 / 136R0273