Thermostat - JUMO miroTRON Operating Manual

Electronic thermostat with pid two-state controller function
Hide thumbs Also See for miroTRON:
Table of Contents

Advertisement

7 Configuration
7.3.5

Thermostat

Thermostat with the setup program and on the device
The device settings for the thermostat and controller function are specified in this menu.
The setup program detects which device version is being used.
When the PID two-state controller option is enabled, it is possible to choose between the thermostat and
PID two-state controller.
Parameter
Controller type
Function
Setpoint value 1
Setpoint value 2
Min. setpoint value -1999.0 to +9999.0
Max. setpoint val-
ue
Setpoint change-
over signal
Switching differen-
tial
Response in case
of a fault
Min. ON
period
Max. ON period
50
Value
Off
Thermostat
Two-state controller
(2-state controller)
Heating
Cooling
-1999.0 to +9999.0
-1999.0 to +9999.0
-1999.0 to +9999.0
Digital selector,
see page 39
0 to +9999.0 °C
Output off
Output on
0 to +9999.0 s
0 to +9999.0 s
Default setting Description
Thermostat
Selection of device function
Heating
Heating:
The thermostat output switches as soon
as the setpoint value is undershot
Cooling:
The thermostat output switches as soon
as the setpoint value is exceeded
0.0
Value of setpoint value 1
0.0
Value of setpoint value 2
-1999.0
Minimum admissible setpoint value
9999.0
Maximum admissible setpoint value
No selection
Signal (high-active) for changeover to
setpoint value 2
1.0
Hysteresis function
Output off
State of the output signal in the case of a
fault
0.0 s
Minimum ON period of the output signal
0.0 s
Maximum ON period of the output signal

Advertisement

Table of Contents
loading

This manual is also suitable for:

701080701081

Table of Contents