Securing The Panel-Mounting Thermostat; Securing The Thermostat Head; Capillary / Temperature Probe / Pocket; General - JUMO KMf-20 Operating Instructions Manual

Panel-mounting thermostats
Table of Contents

Advertisement

3.2

Securing the panel-mounting thermostat

Operating
position

3.2.1 Securing the thermostat head

3.3

Capillary / Temperature probe / Pocket

3.3.1 General

A
H
any
With two screws M4
on the chassis
( 1 ) Screw
( 2 ) Panel
Cutting through or kinking the capillary of the panel-mounting thermostat will
result in permanent instrument failure!
The minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be installed in JUMO pockets, otherwise the
approval of the panel-mounting thermostat becomes invalid.
The temperature probe must be completely immersed in the medium.
To ensure their overall accuracy, the thermostats must only be used together
with the protective pockets supplied by the factory.
Pockets with diameter D = 10 mm may only be fitted with probes with diame-
ter d = 8 mm.
When used in air, the temperature probe A (without pocket) has to be chosen.