7.3.8

Limit value monitoring

Limit value monitoring function 1 to 3 with the setup program and on the device
The device is equipped with 3 limit value monitoring functions that can be individually configured. The
following configuration parameters are available for each of the 3 limit value monitoring functions.
Parameter
Function
?
Actual value input Analog selector,
Setpoint value in-
put
Limit value
Limit value
behavior
Switching behav-
ior
Start-up alarm
suppression
?
Switch-on
delay time
Switch-off
delay time
54
Value
No function
AF1
AF2
AF3
AF4
AF5
AF6
AF7
AF8
see page 40
-9999 to 9999
Symmetrically
Non-standard
Symmetrically
Non-standard left
Non-standard right
Off
On
0 to 9999
0 to 9999
Default setting Description
No (empty)
Limit value above and below the setpoint
value
As for AF1, output signal inverted
Limit value below the setpoint value
As for AF3, output signal inverted
Limit value above the setpoint value
As for AF5, output signal inverted
Fixed limit value independent of the set-
point value
As for AF7, output signal inverted
No selection
Analog value as actual value (signal to be
monitored)
No selection
Analog signal as setpoint value (refer-
ence signal for AF1 to AF6)
0
Admissible deviation (AL) of the actual
value
Symmetrically
Standard of monitoring band for AF1 and
AF2
Standard monitoring band, formed by the
limit value (AL)
Non-standard monitoring band, formed
by the limit value (AL) and limit value 2
(AL2)
Symmetrically
Switching differential position around the
limit value
Switching differential is positioned with
half above and half below the limit value
Switching differential is below the limit
value (typically)
Switching differential is above the limit
value (typically)
Off
Alarm suppression during
start-up phase
Limit value monitoring function always
operates according to its alarm function
Alarm suppression after power on or if
limit value or setpoint value is changed
0
Delay time (in seconds) for activation of
the output signal if alarm condition is
present
0
Delay time (in seconds) for deactivation
of the output signal if alarm condition is no
longer present