Digital Input - JUMO miroTRON Operating Manual

Electronic thermostat with pid two-state controller function
Hide thumbs Also See for miroTRON:
Table of Contents

Advertisement

Parameter
Cold junction tem-
perature
Fine adjustment
(only on device)
Fine adjustment on the device
Actual Start Value -9999 to 9999
Actual end value
Target Start Value -9999 to 9999
target end value
7.3.4

Digital input

Digital input with the setup program and on the device
The settings for the digital input of the device are specified in this menu.
The setup program detects which device version is being used.
Parameter
Inversion
Value
Internal
Constant 0 °C
Off
On
-9999 to 9999
-9999 to 9999
Value
OFF
ON
Default setting Description
Internal
For the thermocouple signal type, either
the internal device temperature (mea-
sured at the terminals on the device) or
the constant 0 °C can be set.
Off
The function for performing fine adjust-
ment is not active.
This function is available in the setup pro-
gram under "Online parameter".
Fine adjustment is active. The following
parameters can be input.
0.0
Fine adjustment: device measured value
at the lower measuring point
100.0
Fine adjustment: device measured value
at the upper measuring point
0.0
Fine adjustment: reference value at the
lower measuring point
100.0
Fine adjustment: reference value at the
upper measuring point
Default setting Description
OFF
When "ON", the switching status is in-
verted.
7 Configuration
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

701080701081