7 Configuration
7.3.3

Analog input

Analog input with the setup program and on the device
The settings for the analog input of the device are specified in this menu.
The setup program detects which device version is being used.
Parameter
Signal type
temp.
Linearization
Scaling start
Scaling end
Decimal
places
Measured value
offset
Lead wire resis-
tance
Filter time con-
stant
48
Value
2L RTD temperature
probe
3L RTD temperature
probe
Thermocouple
0(4) to 20 mA
0 to 10 V
None
Absolute
Relative
Pt100
Pt1000
Fe-CuNi L
Fe-CuNi J
NiCr-Ni K
Linear
Customer-specific
-9999.0 to +9999.0 °C 0 °C
-9999.0 to +9999.0 °C 100 °C
Auto
XXXX.
XXX.X
-9999.0 to +9999.0
0 to 60 Ω
0.0 to 100 s
Default setting Description
The default set-
Sensor type or signal type (depends on
ting depends
the device version)
on the device
version.
For current and voltage (otherwise al-
ways absolute temperature and not edit-
able)
Absolute
Automatic conversion to Fahrenheit no
longer applies
Conversion to Fahrenheit with offset
Offset is not taken into account when con-
verting to Fahrenheit
The default set-
Setting of linearization of the connected
ting depends
sensor
on the device
version.
Only for voltage and current
Customer-specific linearization with 4th
order polynomial or grid points (configu-
rable with setup program)
For signal type 0(4) to 20 mA or
0 to 10 V, you set the temperature range
start and end point to which the signal
should be mapped.
Auto
Number of pre-decimal and decimal plac-
es for the numerical display of the mea-
sured value
For the setting "Auto", the decimal place
is automatically adjusted.
No decimal place
One decimal place
0.0
The entire measuring range is adjusted
up or down
0
Resistive line resistance for two-wire cir-
cuit.
0.6 s
Time constant (in seconds) for adjusting
the digital input filter
(0 s = filter off)