JUMO miroTRON Operating Manual page 55

Electronic thermostat with pid two-state controller function
Hide thumbs Also See for miroTRON:
Table of Contents

Advertisement

Parameter
Pulse time
Response in case
of a fault
Lock
Acknowledge-
ment signal
Function
For the AF1 to AF6 alarm functions, the final limit value depends on the setpoint value – the entered limit
value is added to or subtracted from the setpoint value. The AF7 and AF8 alarm functions work with a
fixed limit value which corresponds to the limit value entered.
See chapter 7.3.8 "Limit value monitoring", Page 54
Startup alarm suppression
Function of the startup alarm suppression:
After power on, the alarm signals for the limit value monitoring function remains inactive, even if the
actual value is in the alarm range.
If the limit value or setpoint value is changed so that the actual value is then within the alarm range,
while the actual value is outside of the alarm range, the alarm signal remains inactive.
The limit value monitoring only starts to operate according to its alarm function again once the actual
value has left the alarm range. This means that the alarm signal remains inactive until the actual val-
ue returns to the alarm range.
Alarm functions
The following tables show the alarm functions AF1 to AF8 and the position of the hysteresis (non-stan-
dard left, standard, non-standard right).
Switching functions in relation to setpoint value
Non-standard left
AF1
1
0
Value
0 to 9999
Output off
Output on
Off
On
Always acknowledge-
able
Digital selector,
see page 39
Symmetrically
(1)
(2)
x
w
Default setting Description
0
The output signal is deactivated automat-
ically after this time (in seconds), even if
the alarm condition is still present. If the
alarm condition occurs again, the function
re-starts (edge-triggered).
Output off
Output signal in the event of a fault (e.g.
in the case of overrange or underrange)
Output signal inactive
Output signal active
Off
Lock is not active. The output signal is re-
set as soon as the actual value is back in
the valid range
Lock is active. Lock can only be acknowl-
edged if the actual value is back in the
valid range
Lock is active. The lock can always be ac-
knowledged
No selection
Signal (high-active) for acknowledging
the output signal in case of locking
1
(1)
(2)
0
w
7 Configuration
Non-standard right
1
(1)
(2)
0
x
w
x
55