Opening The Housing; Fixing The Surface-Mounting Thermostat; Code S (Rigid Stem); Code F (With Capillary) - JUMO ATHf-SW Operating Instructions Manual

Surface-mounting thermostats series ath.-sw-..
Table of Contents

Advertisement

3 Mounting

3.2 Opening the housing

Opening
V
3.3

Fixing the surface-mounting thermostat

Nominal
position (NL)

3.3.1 Code s (rigid stem)

3.3.2 Code f (with capillary)

Fixing the ther-
mostat head
3.4

Capillary / temperature probe / pocket

3.4.1 General

A
H
10
✱ Unscrew the 4 cover screws
✱ Remove housing top
Take care that the seal is seated correctly!
to DIN 16 257, NL 0 — NL 90 (other NL on request)
The housing spigot is secured by a fixing screw in the enlarged pocket open-
ing.
by 4 screws through base of housing,
capillary exit at side of housing
Cutting through or kinking the capillary of the surface-mounting thermostats
will result in permanent instrument failure!
Minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be installed in JUMO pockets, otherwise the
approval of the surface-mounting thermostat becomes invalid.
The temperature probe must be completely immersed in the medium.
To ensure their overall response accuracy, the thermostats must only be used
in conjunction with the pockets supplied by the factory.
When used in air, a process connection without pocket must be chosen.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aths-sw

Table of Contents