Opening The Surface-Mounting Thermostat; Fixing The Surface-Mounting Thermostat; Capillary / Temperature Probe / Pocket; General - JUMO ATH-EXx Operating Instructions Manual

Explosion-protected surface-mounted thermostat
Table of Contents

Advertisement

3 Mounting
3.2

Opening the surface-mounting thermostat

3.3

Fixing the surface-mounting thermostat

Mounting
position
3.4

Capillary / temperature probe / pocket

3.4.1 General

3.4.2 Approved probes and sheaths

10
Unscrew the 4 cover screws (2)
Remove cover (3) with seal (not visible)
Make sure that the seal is seated correctly when reassembling!
To DIN 16257, NL 0 — NL 90 (other NL on request)
Drill fixing holes according to the drilling diagram.
Use the 4 screws to secure the housing base.
Cutting through or kinking the capillary of the surface-mounting thermostat will
lead to permanent instrument failure!
Minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be mounted in a JUMO pocket, otherwise the
approval of the surface-mounting thermostat becomes invalid.
The temperature probe must completely immersed in the medium to be
measured.
To ensure their overall accuracy, the thermostats must only be used together
with the pockets supplied by the factory (diameter D = 8, 10 or 15 mm).
Pockets with a diameter D = 10 mm must only be fitted with probes with
diameter d = 8 mm.
Fitting several probes into a common pocket is only permitted with 2 or 3
probes (mounting type "10", diameter d = 6 mm) and 15 x 0.75 mm pockets.
When fitting 2 probes in a common pocket, the factory-supplied spring clip
must be fitted in the pocket.
For operation in air, probe mounting type "10" (without pocket) must be cho-
sen.
see current data sheet 606710