Digital control signals with the setup program and on the device
The digital control signals for adjusting applications are specified in this menu.
The setup program detects which device version is being used.
Parameter
Function
Digital signal
2nd signal OR/
AND/XOR
3rd signal OR/
AND/XOR
Inversion
Switch-on time/
delay
Switch-off time/
delay
Value
No function
Pulse
Delay
Pulse function
Rising edge
Falling edge
OR function
AND function
XOR function
Digital selector,
see page 39
Digital selector,
see page 39
Digital selector,
see page 39
No
Yes
0 to 9999 s
0 to 9999 s
Default setting
Description
No function
The output signal corresponds to
the input signal (with inverting if
necessary)
A pulse-like signal is output as long
as the input signal is active (high)
The output signal follows the
course of the input signal, whereby
the transfer from low to high status
and vice versa is delayed
For the rising edge of the input sig-
nal, the output signal is activated
and deactivated once the pulse
time has elapsed (even if the input
signal is still active). When the
edge of the input signal rises again,
the function re-starts
The output signal is activated for
the duration of a cycle interval for
the rising edge of the input signal.
The output signal is activated for
the duration of a cycle interval for
the falling edge of the input signal
Logical OR link of the input signals
(signal 1, signal 2, signal 3)
Logical AND link
Logical XOR link
No selection
Input signal (or OR/AND/XOR sig-
nal 1)
No selection
Second input signal for the logical
link
No selection
Third input signal for the logical link
No
Output signal (control signal) not
inverted
Output signal (control signal)
Inverted
0
Pulses: Switch-on time (high sta-
tus; in seconds)
Delay: delay time (in seconds) for
the transition from low to high sta-
tus
0
Pulses: Switch-off time (low status;
in seconds)
Delay: Delay time (in seconds) for
the transition from high to low sta-
tus