Fixing The Panel-Mounting Thermostat; Mounting The Switch Head; Capillary / Temperature Probe / Pocket; General - JUMO KM-70 Operating Instructions Manual

Panel-mounting thermostat
Hide thumbs Also See for KM-70:
Table of Contents

Advertisement

3.2

Fixing the panel-mounting thermostat

Operating
position

3.2.1 Mounting the switch head

3.3

Capillary / temperature probe / pocket

3.3.1 General

A
H
unrestricted
by two M4 screws
on the chassis
( 1 ) Screw
( 2 ) Panel
Cutting through or kinking the capillary of the panel-mounting thermostat will
lead to permanent instrument failure!
The minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be installed in a JUMO pocket, otherwise the
approval of the panel-mounting thermostat becomes invalid.
The temperature probe must be completely immersed in the medium to be
measured.
Temperature probes and pockets must not come into contact with the walls of
the container or pipe.
To ensure their overall accuracy, the thermostats must only be used together
with the pockets supplied by the factory.
Pockets with diameter D = 10 mm may only be fitted with probes with
diameter d = 8 mm.
For operation in air, probe mounting A (without pocket) must be chosen.